DPW-24011-ADM Replace 3 Rooftop Units and 1 Cooling Tower

Replace 3 Rooftop Units and 1 Cooling Tower

Status

Accepting Bids

Prebid Date9/12/24 9:00am

Bid Date10/1/24 11:00am

Company & Contacts

Idaho Division of Public Works
Barry J. Miller  
208-332-1900

Location

Idaho Falls, Idaho

RTU-1 – The existing equipment is an indirect gas fired duct furnace with a modulating outside air intake damper and a modulating return air damper. Relief

air is accomplished by a nearby roof mounted exhaust fan. The supply airflow rate is 4000 CFM and the natural gas heating capacity is 288 MBH output. This

equipment has no cooling capability and no existing electrical infrastructure to support cooling. Replacement equipment will have natural gas fired heating

and controls compatible with the existing controls infrastructure in the building.

RTU-2 – The existing equipment is an indirect gas fired duct furnace with a modulating outside air intake damper and a modulating return air damper. Relief

air is accomplished by a nearby roof mounted exhaust fan. The supply airflow rate is 2200 CFM and the natural gas heating capacity is 162 MBH output. This

equipment has cooling DX cooling with a unit mounted coil and a roof mounted 5-ton nominal condensing unit. Replacement equipment will be a similar

rooftop unit with DX cooling and an associated air-cooled condenser, natural gas fired heating, and controls compatible with the existing controls

infrastructure in the building.

RTU-3 – This equipment is almost identical to RTU-1 and the replacement scope is the same.

Estimated Cost: $400,000